Type FKS-EU

Compact dimensions, ideal for restricted spaces

Small rectangular fire damper for the isolation of duct penetrations between fire compartments, available in many sizes

  • Nominal sizes 200 × 100 to 800 × 200 mm
  • Low differential pressure and sound power level
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Can also be used as an air transfer damper or air transfer unit
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options


Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C
  • Duct smoke detectors

FKS-EU with spring return actuator 00130543_0
  • Application
  • Description

Application

  • Fire dampers of Type FKS-EU, with CE marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire
  • To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments

Special characteristics

  • Declaration of performance according to Construction Products Regulation
  • Classification to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S
  • Building inspectorate licence Z-56.4212-991 for fire resistance properties
  • Complies with the requirements of EN 15650
  • Tested to EN 1366-2 for fire resistance properties
  • Hygiene complies with VDI 6022 part 1 (07/2011), VDI 3803 (10/2002), DIN 1946 part 4 (12/2008), and EN 13779 (09/2007)
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 2
  • Casing air leakage to EN 1751, class C
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central BMS with TROXNETCOM

Classification

  • Class of performance to EN 13501-3, up to EI 120 (ve, ho, i ↔ o) S

Nominal sizes

  • B × H: 200 × 100 – 800 × 200 mm (width in increments of 50 mm)
  • L: 300 mm

Variants

  • With fusible link
  • With spring return actuator
  • With cover grilles both ends as air transfer unit with general building inspectorate licence: Z-19.18-2127
  • With spring return actuator and duct smoke detector
  • With spring return actuator, duct smoke detector and cover grilles on both ends for use as an air transfer opening, with general building inspectorate licence Z-6.50-2231

Parts and characteristics

  • Easy dry mortarless installation into solid walls and ceiling slabs, lightweight partition walls, fire walls and shaft walls using an installation block
  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)

Attachments

  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Network module for the integration with AS-i or LON networks
  • Spring return actuator and pre-wired duct smoke detector, 24 V or 230 V supply voltage

Accessories

  • Cover plate (to keep the fire damper stable and hence facilitate mortaring)
  • Cover grille
  • Flexible connectors
  • Extension piece
  • Rectangular installation block E

Useful additions

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D

Construction features

  • Rectangular or square construction, rigid casing, both flanges with fixing holes (System 30)
  • Suitable for the connection of ducts, flexible connectors or a cover grille
  • The release mechanism is accessible and can be tested from the outside
  • Two inspection access panels
  • Intermediate dimensions in 50 mm increments for width
  • Remote control with spring return actuator

Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:

  • Special insulation material
  • Special insulation material with coating


Other components:

  • Damper blade shaft in stainless steel
  • Plastic bearings
  • Seals of elastomer


The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.

Standards and guidelines

  • Construction Products Regulation
  • EN 15650:2010 Ventilation for buildings – Fire dampers
  • EN 1366-2:1999 Fire resistance tests for service installations – Fire dampers
  • EN 13501-3:2010 Fire classification of construction products and building elements
  • EN 1751:1999 Ventilation for buildings – Air terminal devices

Maintenance

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later.
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule of the ventilation system.
  • For details on maintenance and inspection refer to the installation and operating manual

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.


Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Visual contact Visual contact

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Visual contact Visual contact

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call: