Shut-off damper Type AK-Ex


00135111_0
ATEX-Zertifizierung


00130917_0
ATEX-compliant parts and units


00136579_0
00135111_0
00130917_0

AK-EX    

FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

Circular shut-off dampers for shutting off ducts, approved and certified for potentially explosive atmospheres (ATEX)

  • ATEX-compliant construction and parts
  • Approved for all gases, mists and vapours in zones 1 and 2, with electric actuator additionally for dusts in zones 21 and 22
  • Suitable for supply air and extract air
  • Electric or pneumatic actuator
  • Any installation orientation
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, class C


Optional equipment and accessories

  • Spring return actuator
  • Auxiliary switch with adjustable switching points for capturing the end positions

General information

Application

  • Circular EXCONTROL shut-off dampers Type AK-Ex for shutting off or restricting the airflow in ventilation ducts of air conditioning systems
  • For use in potentially explosive atmospheres (ATEX)
  • Input signal to control shut-off damper blade is to be provided by others

Special features

  • ATEX mark and certification
  • ATEX equipment group II, approved for use in zones 1 and 2; electric actuator also for zones 21 and 22


Nominal sizes

  • 125, 160, 200, 250, 315, 400


Construction

  • Galvanised sheet steel
  • P1: Inner duct powder-coated, silver grey (RAL 7001)
  • A2: Inner duct in stainless steel

Parts and characteristics

  • Ready-to-install shut-off damper
  • Damper blade with blade mechanism
  • Connection for equipotential bonding
  • Cable bushings suitable for use in potentially explosive atmospheres
  • ATEX-compliant actuator is factory assembled and wired

Attachments

  • Electronic actuator:
  • Auxiliary switch for capturing the end positions
  • Pneumatic actuator

Construction features

  • Circular casing
  • Construction and materials comply with the EU directive for use in potentially explosive atmospheres (ATEX)
  • Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180


Technical data

  • Nominal sizes: 125 – 400 mm
  • Acceptable static differential pressure: 1500 Pa

Standards and guidelines

  • Directive 94/9/EC: Equipment and protective systems intended for use in potentially explosive atmospheres
  • Closed blade air leakage to EN 1751, class 4 (nominal sizes 100 and 160, class 3)
  • Nominal sizes 125 and 160 meet the general requirements, nominal sizes 200 – 400 meet the increased requirements of DIN 1946, part 4, with regard to the acceptable closed blade air leakage
  • Casing air leakage to EN 1751, class C

Maintenance

  • Maintenance-free as construction and materials are not subject to wear

Technical information

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Nominal sizes

125 – 400 mm

Acceptable static differential pressure

1500 Pa

Operating temperature

10 – 50 °C


Electronic

Supply voltage

24 – 230 V AC ± 10 %, 50/60 Hz

Power rating

120 VA max.

IEC protection class

I (protective earth)

Protection level

IP 42

EC conformity

ATEX to 2014/34/EU, EMC to 2014/30/EU, low voltage to 2014/35/EU


Pneumatic

Control pressure

0 – 1.2 bar

Maximum pressure

1.5 bar

Compressed air

Compressed air for instruments, free of oil, water and dust

Protection level

IP 42

Air consumption (100 % stroke)

0.3 l/n (nominal sizes 125 – 250) to 0.5 l/n max. (nominal size 315 – 400)

EC conformity

ATEX to 2014/34/EU


This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.


Circular shut-off dampers for shutting off or restricting the airflow in potentially explosive atmospheres, for supply air or extract air, available in 6 nominal sizes.

Suitable for duct pressures up to 1500 Pa.

Ready-to-install unit consists of the casing with damper blade, and parts for equipotential bonding and for use in potentially explosive atmospheres.

Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180.

Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).

Casing air leakage to EN 1751, class C.

Special features

  • ATEX mark and certification
  • ATEX equipment group II, approved for use in zones 1 and 2; electric actuator also for zones 21 and 22

Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Blade seal made of TPE plastic
  • Plain bearings made of polyurethane
  • Electric actuator made of die cast aluminium
  • Pneumatic actuator made of plastic
  • Inner tube either made of stainless steel 1.4301 (A2) or powder-coated (P1)

Construction

  • Galvanised sheet steel
  • P1: Inner duct powder-coated, silver grey (RAL 7001)
  • A2: Inner duct in stainless steel

Technical data

  • Nominal sizes: 125 – 400 mm
  • Acceptable static differential pressure: 1500 Pa

Sizing data

  • qᵥ [m³ /h]
Air-regenerated noise
  • LPA [dB(A)]

1 Type
AK-Ex Shut-off damper for potentially explosive atmospheres


2 Material
No entry: galvanised sheet steel
P1 Inner duct powder-coated, RAL 7001 (silver grey)
A2 Inner duct in stainless steel


3 Nominal size [mm]
125, 160, 200, 250, 315, 400


4 Actuator
Electric
T0S Actuator
T0F Spring return actuator
T0X Actuator with auxiliary switch
T0Y Spring return actuator with auxiliary switch


Pneumatic
P50 Actuator


5 Damper blade position
Only with spring return actuator or pneumatic actuator
NO pressure off/power off to OPEN (Normally Open)
NC power off/pressure off to CLOSE (Normally Closed)


Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34