Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

X-AIRCONTROL zone master module for the control of zone modules and as an interface to higher-level systems such as air handling units and central BMS

  • Optimisation of control functions to achieve a comfortable and energy-efficient operation of ventilation and air conditioning systems
  • One zone master module and up to 25 zone modules form a segment
  • Up to five cascading master modules form a section with up to 125 zone modules
  • Communication between master modules, and between master and zone modules, is by plug and play
  • Web server for configuration and operation; user interface optimised also for mobile devices
  • Modbus TCP and BACnet IP interfaces to higher-level systems such as the central BMS
  • Modbus RTU interface to air handling units Type X-CUBE compact
  • Connection of signals, e.g. outdoor air temperature and fire alarm
  • Output of signals, e.g. requests and alarms

Application

Application

  • X-AIRCONTROL zone master module Type X-AIR-ZMAS, for the provision of control signals to zone modules and as an interface to higher-level systems
  • Centralised parameter setting for, and operation and monitoring of, zone modules
  • For use in office buildings, hotels, residential buildings and others
  • One zone master module can be used to control a segment of up to 25 zone modules
  • Up to five cascading master modules form a section with up to 125 zone modules
  • For the connection of up to 25 zone modules to air handling units Type X-CUBE compact (only 4 zone modules if no master module is used)
  • Communication between master modules, and between master and zone modules, is by plug and play
  • Web server for configuration and operation; user interface optimised also for mobile devices
  • Modbus TCP and BACnet IP interfaces to higher-level systems such as the central BMS
  • Optimum number of data points allows for easy administration in higher-level systems
  • Plug and play interface to air handling units Type X-CUBE compact
  • Connection of signals, e.g. outdoor air temperature and fire alarm
  • Output of signals such as operating states, requests and alarms
  • Demand-based activation of the supply or extract air fan, depending on the damper blade positions or pressures in the supply or extract air system
  • Pressure control or limitation in the supply air and extract air systems
  • Energy-efficient operation of the air handling unit as a consequence of demand-based default settings (fan speed, supply air temperature setpoint); the default settings result from the evaluation of parameters sent by zone modules (e.g. damper blade positions, required heating, required cooling)
  • Temperature setpoint shifting based on the outdoor air temperature (summer and winter compensation)
  • Central alarm management; configuration display for all rooms in a section, e.g. display of actual and setpoint values
  • Central device for firmware updates for a section

Special characteristics

  • Plug and play system which automatically detects master and zone modules
  • Energy-efficient operation of the air handling unit (fan speed, supply air temperature setpoint) as a consequence of the evaluation of parameters sent by zone modules
  • Web server for configuration and operation; user interface optimised also for mobile devices
  • Modbus TCP and BACnet IP interfaces to higher-level systems such as the central BMS; central signalling of higher-level data
  • For the connection of up to 25 zone modules to air handling units Type X-CUBE compact (only 4 zone modules if no master module is used)
  • Plug connections or plug-in screw terminals

Description

Parts and characteristics

  • Micro processor system with software and system data stored in non-volatile memory
  • Supply voltage 24 V AC
  • Integral webserver for configuration and operation
  • Modbus TCP and BACnet IP interfaces for the exchange of data with higher-level systems
  • Modbus RTU interface for the exchange of data with an air handling unit (plug and play with X-CUBE compact)
  • Two interfaces for the connection of another two zone master modules
  • Digital inputs with plug-in screw terminals
  • Digital outputs with plug-in screw terminals
  • Temperature input with plug-in screw terminals
  • Analog outputs with plug-in screw terminals
  • Slot for SD cards (SDHC) of up to 8 GB
  • 2 GB SD card

Useful additions

  • Zone modules X-AIR-ZMO-MOD, X-AIR-ZMO-MP, X-AIR-ZMO-ANA
  • Temperature sensor X-SENS-TEMP-PT1000

Construction features

  • Casing fits on mounting rails
  • All connections are at the outside

Materials and surfaces

  • Plastic casing

Technical information

Function, Technical data, Specification text, Order code

  • Function
  • Technical data
  • Specification text
  • Order code
X-AIRCONTROL segment 00236776_0
① Zone modules
② Master module
③ WiFi router
④ Smartphone or tablet
Central BMS


Functional description

The X-AIR-ZMAS zone master module is used for the integration and configuration of up to 25 zone modules; 25 zone modules and the zone master module form a segment.

The zone master module includes a webserver. The webserver is used to access a web browser (e.g. Internet Explorer or Mozilla Firefox) for the configuration display and operation of the zone master. Interfaces to higher-level systems and to an air handling unit are used for exchanging data with those systems. The zone master module has inputs and outputs for the integration of components that are relevant to the entire segment.

Up to five cascading master modules form a section with up to 125 zone modules. The first master module in such a chain is the highest-level master, with higher-level functions. This highest-level master performs functions for the entire section, such as controlling the fans and releasing heating and cooling requests. All other functions of the zone master module apply only to the respective segment.

Signals and functions

  • Outdoor air temperature sensor: Summer or winter compensation for all zone modules is based on the outdoor air temperature.
  • Fire alarm: Signal from the central fire alarm system for the (override) control of all VAV terminal units in a segment; the function can be configured: supply air Vmax or shut-off, extract air Vmax or shut-off
  • Release of zones: Switching between Standby and Automatic mode for all zones
  • Alarm signal from the supply air and extract air fans: For signalling to the central BMS
  • Supply air fan activation: Control of the supply air fan, based on demand and on the actual damper blade positions of all supply air terminal units (only if X-AIR-ZMO-MOD or X-AIR-ZMO-MP is included in the segment); if required, including pressure limitation in the supply air system (only with a duct pressure sensor, which is a useful addition)
  • Supply air fan activation: Control of the supply air fan for constant pressure control in the supply air system (only if X-AIR-ZMO-ANA is included in the segment, and only with a duct pressure sensor, which is a useful addition)
  • Extract air fan activation: Control of the extract air fan, based on demand and on the actual damper blade positions of all extract air terminal units (only if X-AIR-ZMO-MOD or X-AIR-ZMO-MP is included in the segment); if required, including pressure limitation in the extract air system (only with a duct pressure sensor, which is a useful addition)
  • Extract air fan activation: Control of the extract air fan for constant pressure control in the extract air system (only if X-AIR-ZMO-ANA is included in the segment, and only with a duct pressure sensor, which is a useful addition)
  • Cooling fluid temperature sensor: Optimised operation of the cooling circuit as the pump is triggered based on the valve position; alarm output if the configured temperature value is exceeded (only X-AIR-ZMO-MOD or X-AIR-ZMO-MP)
  • Cooling request output: The output is active if at least one zone requests cooling
  • Heating request output: The output is active if at least one zone requests heating
  • Operating mode output: The output is active when all zones are in Automatic mode
  • Alarm output: Major fault (A alarm, leads to the system being switched off) or minor fault (B alarm)

Operating modes

  • Automatic: Demand-based zone control
  • Minimum volume flow rate: All volume flow controllers are set to Vmin, temperature control and control of heating and cooling valves remain active
  • Maximum volume flow rate: All volume flow controllers are set to Vmax, temperature control and control of heating and cooling valves remain active
  • Fire alarm: Supply air Vmax or shut-off, extract air Vmax or shut-off
  • Standby: All volume flow controllers are shut off, heating and cooling valves are closed

Interfaces, The system, Product details

  • Interfaces
  • The system
  • Product details

Inputs

6 digital inputs

  • Supply air fan alarm
  • Extract air fan alarm
  • Release of zones
  • Fire alarm
  • Override control Vmax
  • Override control Vmin


2 inputs for temperature sensors

  • Cooling fluid temperature sensor PT1000
  • Outdoor air temperature sensor PT1000

Outputs

5 digital outputs

  • Release of cooling function
  • Release of heating function
  • Operating mode
  • Major fault alarm (leads to the system being switched off)
  • Minor fault alarm

3 analog outputs

  • Supply air fan
  • Extract air fan
  • Cooling fluid pump

SD card reader

  • SD card reader for standard SDHC cards of up to 8 GB

Communication interfaces

  • Ethernet to central BMS
  • Modbus to zone modules
  • Modbus to cascading zone master modules
  • Modbus to air handling unit


Installation details, Basic information and nomenclature

  • Installation details

Installation and commissioning

  • Screw-fix the module inside a switch cabinet or to a wall or ceiling, or mount it onto a mounting rail
  • zone modules (in series) using flat cables with RJ12 plugs (6P6C)
  • Connect externel components, if any
  • Connect the 24 V AC supply voltage
  • Adapt the standard IP address, if necessary (no additional device addressing required)
  • Adapt the configuration by using the webserver (access is password protected)
  • Take account of the network wiring (IP) and infrastructure


Downloads

product information

operation manuals

software

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34