img_pro_000541.png
Mini Pleat filter panels, type MFP

doc_graphic_000009.png
Tested to VDI 6022

Tested to VDI 6022

Eurovent_Filter_Marketing_Highlight.ai.png
Eurovent-Zertifizierung

Eurovent certification

img_pro_000541.png
doc_graphic_000009.png
Eurovent_Filter_Marketing_Highlight.ai.png

Type MFP

For the most demanding requirements of air cleanliness and sterility


 

Prefilters or final filters for the separation of fine dust and suspended particles. Used for industrial, research, medical, pharmaceutical, and nuclear engineering applications.

  • Filter groups ISO ePM10, ISO ePM1 (fine dust filter) and EPA, HEPA (particulate filter)
  • Performance data tested according to ISO 16890 or  to EN 1822-1 and ISO 29463-2 to ISO 29463-5
  • Eurovent certification for fine dust filters
  • Meets the hygiene requirements of VDI 6022
  • Filter media for special requirements, glass fibre papers with spacers made of thermoplastic hot-melt adhesive
  • Low initial differential pressure due to ideal pleat position and largest possible filter area
  • Perfect adjustment to individual requirements due to different pleat depths, filter frame made of various materials
  • Fitting into ceiling mounted or wall mounted particulate filters (types TFC, TFW, TFM, TFP), ducted particulate filters (types KSF, KSFS), duct casings for particulate filters (type DCA), or operating theatre ceilings
  • Automatic filter scan test for all filters from filter class H14

 

 

 


Introduction

Application

  • Mini Pleat filter panel type MFP for the separation of fine dust and suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply and extract air in ventilation systems with large volume flow rates and the requirement for long filter life
  • Fine dust filter: Prefilter or final filter for the separation of fine dust in ventilation systems.
  • Particulate filter: Main or final filter used for the most critical requirements of air cleanliness and sterility in areas such as industry, research, medicine, pharmaceuticals, and nuclear engineering

Special characteristics

  • Leakage test is standard for all particulate filters of classes H13, H14

Classification

  • Eurovent certification for fine dust filters
  • Constructions ALN, ALZ, ALY, ALU and ALV meet hygiene requirements

Nominal sizes

  • B × H × D [mm]


Description

Construction

  • PLA: Frame made of plastic (depth 48, 96 and 150 mm)
  • MDFF: Frame made of MDF, with header frame (depth 60 mm)
  • MDF: Frame made of MDF (depth 60, 78, 150 and 292 mm)
  • GAL: Frame made of galvanised steel (depth 60, 150 and 292 mm)
  • STA: Frame made of stainless steel (depth 60, 150 and 292 mm)
  • ALN: Frame made of extruded aluminium sections (depth 30 mm)
  • ALZ: Frame made of extruded aluminium sections (depth 78 mm)
  • ALY: Frame made of extruded aluminium sections (depth 150 mm)
  • ALU: Frame made of extruded aluminium sections (depth 91 mm)
  • ALV: Frame made of extruded aluminium sections (depth 85 mm)


Options
▪ FT: Pleat depth
▪ PU: Protection grid on the upstream side
▪ PD: Protection grid on the downstream side
▪ PB: Protection grid on both sides
▪ FNU: Flat seal on the upstream side
▪ FND: Flat seal on the downstream side
▪ FNB: Flat seal on both sides
▪ TGU: Test groove seal on the upstream side (only for filterclasses H13, H14)
▪ CSU: Continuous seal on the upstream side
▪ CSD: Continuous seal on the downstream side
▪ CSB: Continuous seal on both sides
▪ GPU: Fluid seal (only for ALU/ALV)
▪ WS: Without seal
▪ OT: Oil mist test (only for filter classes H13, H14)
▪ OTC: Oil mist test with certificate (only for filter classes H13,H14)
▪ ST: Scan test (only for filter classes H13, H14)


Useful additions

  • Filter wall (SIF)
  • Universal casing (UCA)
  • Ducted particulate filter, available as one unit (KSF, KSFS) or as a filter unit system (KSFSSP)
  • Duct casing for particulate filters (DCA)
  • Ceiling mounted particulate filter (TFC)
  • Wall mounted particulate filter (TFW)
  • Particulate filter module (TFM)
  • Pharmaceutical clean room terminal filter (TFP)

Construction features
  • Perimeter flat seal on the upstream side for constructions MDF, GAL, STA, ALN, ALZ and ALY
  • Some constructions with optional foamed continuous seal or with a test groove seal (filter classes H13, H14) on the upstream side; the flat section or continuous seal can also be fitted on the downstream side or on both sides
  • As standard, constructions ALU/ALV are fitted with a fluid seal
  • Protection grid made of expanded metal, can be fitted on the downstream or upstream side or both sides as required


Materials and surfaces
  • Filter media made of high-quality, moisture-resistant glass fibre papers, pleated
  • Spacers provide a uniform spacing of the pleats
  • Joint sealing compound made of permanently elastic two-component polyurethane adhesive
  • Frame made of either plastic, MDF, galvanised sheet steel, stainless steel, or extruded aluminium sections


Standards and guidelines
  • Test according to ISO 16890; international standard for general room air distribution; classification of arrestance efficiency based on the measured fractional arrestance efficiency, which is processed into a reporting system for the fine dust arrestance efficiency (ePM)
  • For fine dust filters, the fractional arrestance efficiency of a certain size range is determined by aerosols (DEHS and KCl)
  • The filters are classified into filter groups ISO ePM10 and ISO ePM1 depending on the tested values
  • Testing of particulate filters to EN 1822 (EPA, HEPA and ULPA filters): European standard for the testing of filtration performance in the factory, particle counting method using a liquid test aerosol
  • Uniform classification of particulate filters according to efficiency, using a test aerosol whose average particle size lies within the minimum efficiency (MPPS)
  • Particulate filters are classified according to the values determined for the local filtration efficiency and the overall filtration efficiency as EPA (filter classes E10, E11, E12), HEPA (filter classes H13, H14) or ULPA (filter classes U15, U16, U17)
  • Constructions ALN, ALZ, ALY, ALU and ALV meet the hygiene requirements of VDI 6022, VDI 3803, DIN 1946, part 4, ÖNORM H 6020, SWKI VA 104-01, SWKI 99-3, and EN 16798



Technical information

Technical data, SPECIFICATION TEXT, Order code

  • Technical data
  • SPECIFICATION TEXT
  • ORDER CODE

Fractional efficiency ePM10 [%] to ISO 1689075
Fractional efficiency ePM1 [%] to ISO 168906590
Initial differential pressure [Pa] at nominal volume flow rate90110150
Recommended final differential pressure [Pa]450450450
Max. operating temperature [°C]808080
Maximum relative humidity [%]100100100

 

Filter class according to EN 1822E11H13H14
Efficiency [%] according to EN 1822> 95> 99.95> 99.995
Initial differential pressure [Pa] at nominal volume flow rate125250120/140
Recommended final differential pressure [Pa]300600300
Max. operating temperature [°C]808080
Maximum relative humidity [%]100100100



Specification text

Mini Pleat filter panels MFP for the separation of fine dust and suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply and extract air in ventilation systems. Use as fine dust filters, i.e. as prefilters or final filters in ventilation systems; or as particulate filters, i.e. main or final filters for the most critical requirements of air cleanliness and sterility in areas such as industry, research, medicine, pharmaceuticals, and nuclear engineering. Compact depth construction, suitable for systems with high volume flow rates and a requirement for long filter life. The filter media are made of high-quality, moisture-resistant glass fibre papers, with spacers made of thermoplastic hot-melt adhesive. Low initial differential pressure due to ideal pleat position and largest possible filter area. Mini Pleat filter panels available in standard and special sizes, in variable pleat depths, filter groups ISO ePM10, ISO ePM2.5, ISO ePM1 (fine dust filter) and EPA, HEPA, ULPA (particulate filter). Depending on the frame design, Mini Pleat filter panels are fitted with no seal, with a flat seal on the upstream side, or with a fluid seal. Some constructions are available with an optional foamed continuous seal on one or both sides, with a test groove seal on the upstream side, or with a protection grid, fitting as required. Mini Pleat filter panels used as fine dust filters are certified by Eurovent. Constructions with a frame made of extruded aluminium sections meet the hygiene requirements of VDI 6022.



Special Characteristics

  • Leakage test is standard for all particulate filters of classes H13, H14



Materials and surfaces

  • Filter media made of high-quality, moisture-resistant glass fibre papers, pleated
  • Spacers provide a uniform spacing of the pleats
  • Joint sealing compound made of permanently elastic two-component polyurethane adhesive
  • Frame made of either plastic, MDF, galvanised sheet steel, stainless steel, or extruded aluminium sections


Construction
PLA: Frame made of plastic (depth 48, 96 and 150 mm)
MDFF: Frame made of MDF, with header frame (depth 60 mm)
MDF: Frame made of MDF (depth 60, 78, 150 and 292 mm)
GAL: Frame made of galvanised steel (depth 60, 150 and 292 mm)
STA: Frame made of stainless steel (depth 60, 150 and 292 mm)
ALN: Frame made of extruded aluminium sections (depth 30 mm)
ALZ: Frame made of extruded aluminium sections (depth 78 mm)
ALY: Frame made of extruded aluminium sections (depth 150 mm)
ALU: Frame made of extruded aluminium sections (depth 91 mm)
ALV: Frame made of extruded aluminium sections (depth 85 mm)


Sizing data
  • Filter group [ISO 16890]
  • Efficiency [%]
  • Filter class [EN 1822]
  • Volume flow rate [m³/h]
  • Initial differential pressure [Pa]
  • Nominal size [mm]

MFPePM190%MDF / 610 × 610 × 78×50 / PD / FNU / ST
|||||||||
123456789

1 Type
MFP Mini Pleat filter panel
 
2 Filter class
ePM10 Fractional efficiency ePM10 to ISO 16890
ePM1 Fractional efficiency ePM1 to ISO 16890
E11  Particulate filter according to EN 1822
H13 Particulate filter according to EN 1822
H14 Particulate filter according to EN 1822
 
3 Efficiency [%]
according to ISO 16890 (not with E11, H13, H14)
 
4 Construction
PLA Frame made of plastic
MDFF Frame made of MDF, with header frame
MDF Frame made of MDF
GAL Frame made of galvanised steel
STA Frame made of stainless steel
ALN Frame made of extruded aluminium sections (depth 30 mm)
ALZ Frame made of extruded aluminium sections (depth 78 mm)
ALY Frame made of extruded aluminium sections (depth 150 mm)
ALU Frame made of extruded aluminium sections (depth 91 mm)
ALV Frame made of extruded aluminium sections (depth 85 mm)
 
5 Nominal size [mm]
B × H × T
 
6 Pleat depth [mm]
FT
 
7 Protection grid
No entry: none
PU Protection grid on the upstream side
PD Protection grid on the downstream side (Standard in ALN)
PB Protection grid on both sides
 
8 Seal
WS without seal
FNU Flat seal on the upstream side
FND Flat seal on the downstream side
FNB Flat seal on both sides
TGU Test groove seal on the upstream side
CSU Continuous seal on the upstream side
CSD Continuous seal on the downstream side
CSB Continuous seal on both sides
GPU Fluid seal (only for ALU/ALV)
 
9 Testing
No entry: no leakage test
OT Oil mist test (only for filter classes H13, H14)
OTC Oil mist test with certificate (only for filter classes H13, H14)
ST Scan test (only for filter classes H13, H14)



MFP–H13–MDF/610×610×78×50/PD/FNU/ST
Filter class H13 Particulate filter according to EN 1822
Construction Frame made of MDF
Nominal size 610 × 610 × 78 mm
Pleat depth 50
Protection grid downstream side
Seal Flat seal on the upstream side
Test scan test


   

​Dimensions

  • Dimensions
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
2872874840ePM10 75 %139500901,71
2875924840ePM10 75 %3061100903,51
4905924840ePM10 75 %5642030906,22
5925924840ePM10 75 %6942500907,52
2872874840ePM1 65% 1395001101,71
2875924840ePM1 65% 30611001103,51
4905924840ePM1 65% 56420301106,22
5925924840ePM1 65% 69425001107,52
2872874840ePM1 90 %1395001501,71
2875924840ePM1 90 %30611001503,51
4905924840ePM1 90 %56420301506,22
5925924840ePM1 90 %69425001507,52
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
2872879680ePM10 75 %186670902,41
2875929680ePM10 75 %41715009052
4905929680ePM10 75 %7692770908,83
5925929680ePM10 75 %94434009010,74
2872879680ePM1 65 %1866701102,41
2875929680ePM1 65 %417150011052
4905929680ePM1 65 %76927701108,83
5925929680ePM1 65 %944340011010,74
2872879680ePM1 90 %1866701502,41
2875929680ePM1 90 %417150015052
4905929680ePM1 90 %76928801508,83
5925929680ePM1 90 %944340015010,74
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
287287150120ePM10 75% 150540902,21
287592150120ePM10 75% 3781360905,13
490592150120ePM10 75% 7562720909,64
592592150120ePM10 75% 94434009011,85
287287150120ePM1 65% 1505401102,21
287592150120ePM1 65% 37813601105,13
490592150120ePM1 65% 75627201109,64
592592150120ePM1 65% 944340011011,85
287287150120ePM1 90 %1505401502,21
287592150120ePM1 90 %37813601505,13
490592150120ePM1 90 %75627201509,64
592592150120ePM1 90 %944340015011,85
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
2875926046ePM10 75 %3031090903,22
5925926046ePM10 75 %6942500907,34
2875926046ePM1 65% 30310901103,22
5925926046ePM1 65% 69425001107,34
2875926046ePM1 90 %30310901503,22
5925926046ePM1 90 %69425001507,34
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3056106046ePM10 75 %3891400903,82
6106106046ePM10 75 %8333000908,23
7626106046ePM10 75 %105638009010,34
3056106046ePM1 65% 38914001103,82
6106106046ePM1 65% 83330001108,23
7626106046ePM1 65% 1056380011010,34
3056106046ePM1 90 %38914001503,82
6106106046ePM1 90 %83330001508,23
7626106046ePM1 90 %1056380015010,34
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3056106050ePM10 75 %3891400904,53
6106106050ePM10 75 %8333000909,13
7626106050ePM10 75 %105638009011,44
3056106050ePM1 65% 38914001104,53
6106106050ePM1 65% 83330001109,13
7626106050ePM1 65% 1056380011011,44
3056106050ePM1 90 %38914001504,53
6106106050ePM1 90 %83330001509,13
7626106050ePM1 90 %1056380015011,44
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053057846ePM10 75 %182655901,82
3453457846ePM10 75 %240865902,32
4354357846ePM10 75 %4011445903,92
4574577846ePM10 75 %4471610904,43
5355357846ePM10 75 %6292265906,23
5755757846ePM10 75 %7352645907,23
3056107846ePM10 75 %3891400903,83
6106107846ePM10 75 %8333000908,24
3053057846ePM1 65% 1826551101,82
3453457846ePM1 65% 2408651102,32
4354357846ePM1 65% 40114451103,92
4574577846ePM1 65% 44716101104,43
5355357846ePM1 65% 62922651106,23
5755757846ePM1 65% 73526451107,23
3056107846ePM1 65% 38914001103,83
6106107846ePM1 65% 83330001108,24
3053057846ePM1 90 %1826551501,82
3453457846ePM1 90 %2408651502,32
4354357846ePM1 90 %40114451503,92
4574577846ePM1 90 %44716101504,43
5355357846ePM1 90 %62922651506,23
5755757846ePM1 90 %73526451507,23
3056107846ePM1 90 %38914001503,83
6106107846ePM1 90 %83330001508,24
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
6106103020E111495351255,13
7626103020E111896801256,43
9156103020E112288201257,74
12206103020E11308111012510,35
6106103020H131495352505,13
7626103020H131896802506,43
9156103020H132288202507,74
12206103020H13308111025010,35
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053057850ePM10 75 %182655902,22
3453457850ePM10 75 %240865902,92
4354357850ePM10 75 %4011445904,62
4574577850ePM10 75 %4471610905,13
5355357850ePM10 75 %62922659073
5755757850ePM10 75 %7352645908,13
3056107850ePM10 75 %3891400904,53
6106107850ePM10 75 %8333000909,24
3053057850ePM1 65% 1826551102,22
3453457850ePM1 65% 2408651102,92
4354357850ePM1 65% 40114451104,62
4574577850ePM1 65% 44716101105,13
5355357850ePM1 65% 629226511074
5755757850ePM1 65% 73526451108,13
3056107850ePM1 65% 38914001104,53
6106107850ePM1 65% 83330001109,24
3053057850ePM1 90 %1826551502,22
3453457850ePM1 90 %2408651502,92
4354357850ePM1 90 %40114451504,62
4574577850ePM1 90 %44716101505,13
5355357850ePM1 90 %629226515073
5755757850ePM1 90 %73526451508,13
3056107850ePM1 90 %38914001504,53
6106107850ePM1 90 %83330001509,24
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053057850E11722601252,42
3453457850E11963451253,12
4354357850E1116057512552
4574577850E111786401255,53
5355357850E112509001257,63
8355357850E11400144012511,94
11355357850E11551198512516,25
5575577850E112729801258,23
5755757850E1129210501258,83
3056107850E111545551254,93
4576107850E112428701257,43
6106107850E1133111901259,94
7626107850E11418150512512,44
9156107850E11507182512514,95
12206107850E11683246012519,86
3053057850H13722602502,42
3453457850H13963452503,12
4354357850H1316057525052
4574577850H131786402505,53
5355357850H132509002507,63
8355357850H13400144025011,94
11355357850H13551198525016,25
5575577850H132729802508,23
5755757850H1329210502508,83
3056107850H131545552504,93
4576107850H132428702507,43
6106107850H1333111902509,94
7626107850H13418150525012,44
9156107850H13507182525014,95
12206107850H13683246025019,86
3053057850H14361301202,72
3453457850H14491751203,52
4354357850H14812901205,52
4574577850H14903251206,13
5355357850H141264551208,43
8355357850H1420373012013,24
11355357850H14281101012017,95
5575577850H141395001209,13
5755757850H141495351209,73
3056107850H14782801205,53
4576107850H141244451208,23
6106107850H14168605120114
7626107850H1421376512013,74
9156107850H1425893012016,55
12206107850H143421230120226
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
30530515050E11722601252,13
34534515050E11963451252,84
43543515050E111605751254,55
45745715050E1117864012555
53553515050E1125090012576
57557515050E1129210501258,27
30561015050E111545551254,45
45761015050E112428701256,86
61061015050E1133111901259,28
76261015050E11418150512511,69
91561015050E1150718251251411
122061015050E11683246012518,913
30530515050H13722602502,13
34534515050H13963452502,84
43543515050H131605752504,55
45745715050H1317864025055
53553515050H1325090025076
57557515050H1329210502508,27
30561015050H131545552504,45
45761015050H132428702506,86
61061015050H1333111902509,28
76261015050H13418150525011,69
91561015050H1350718252501411
122061015050H13683246025018,913
30530515068H13903252502,84
34534515068H131194302503,65
43543515068H132017252505,95
45745715068H132248052506,66
53553515068H1331411302509,27
57557515068H13367132025010,78
30561015068H131947002505,85
45761015068H1330611002508,96
61061015068H13417150025012,18
76261015068H13528190025015,210
91561015068H13639230025018,411
122061015068H13861310025024,714
305305150120H131284602504,34
345345150120H131686052505,75
435435150120H1328110102509,35
457457150120H13313112525010,36
535535150120H13440158525014,47
575575150120H13514185025016,78
305610150120H132729802509,16
457610150120H134281540250147
610610150120H13583210025018,99
762610150120H13739266025023,811
915610150120H13894322025028,712
1220610150120H131206434025038,615
305305150120H14692501404,34
345345150120H14923301405,75
435435150120H141545551409,35
457457150120H1417161514010,36
535535150120H1424287014014,47
575575150120H14282101514016,78
305610150120H141495351409,16
457610150120H14233840140147
610610150120H14319115014018,99
762610150120H14404145514023,811
915610150120H14490176514028,712
1220610150120H14660237514038,615
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053059150H13722602502,42
3453459150H13963452503,12
4354359150H1316057525052
4574579150H131786402505,53
5355359150H132509002507,63
8355359150H13400144025011,94
11355359150H13551198525016,25
5755759150H1329210502508,83
6106109150H1333111902509,94
3053059150H14361301202,72
3453459150H14491751203,52
4354359150H14812901205,52
4574579150H14903251206,13
5355359150H141264551208,43
8355359150H1420373012013,24
11355359150H14281101012017,95
5755759150H141495351209,73
6106109150H14168605120114

Downloads

product information

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34