CFE-T-PP_gc_10psd.png
CFE-T-PP
CFE_gc_18psd.png

Design options

with perforated sheet cover or

slot diffuser face

CFE-T_gc_19ai.png
<strong>CFE-T-PP/SC, installation in lightweight partition wall</strong>

T-style construction, for lightweight partition walls

CFE_Z_gc_25ai.png

Z-style construction, for lightweight partition walls

cfe_gc_23psd.png

Installation in lightweight partition walls
with metal support structure

CFE-T-PP_gc_10psd.png
CFE_gc_18psd.png
CFE-T_gc_19ai.png
CFE_Z_gc_25ai.png
cfe_gc_23psd.png

CFE   

Free design options for builders and architects with high aesthetic demands

Crossflow element in different variants

  • With recess for air diffusers – with fronts with different optics
  • Without recess for air diffusers – for free design options in the choice of wall opening
  • With integrated cross talk silencer and sealing strips for sound insulation
  • Nominal lengths from 550 - 1175 mm in mm steps
  • Nominal heights from 290 - 440 mm in mm steps
  • The wide range of dimensions allows a large selection of different installation situations, with low pressure loss and high sound insulation values
  • Installation in lightweight partition walls with a thickness of 100 mm or 125 mm and with 50 mm or 75 mm wide metal frame

 

Optional equipment


  • Diffuser face powder-coated in RAL CLASSIC colours

General information

Application

  • Crossflow elements are suitable as cross talk silencers for air transfer flows in comfort zones
  • Due to their diversity of variants and high flexibility, they can be used for many applications


Special features

  • Different construction styles allow individual adaptation to local conditions
  • Low differential pressure
  • Crossflow elements in T- and Z-design without recess for an air diffuser are suitable for (system) partition walls
  • Cross talk silencers reduce noise transmission to adjacent rooms
  • To prevent sound transmission via the casing, insulation strips are attached to the crossflow element
  • Tool-free assembly of the diffuser face enables quick installation after completion of the drywall work
  • High-quality appearance of diffuser face due to powder coating according to RAL-CLASSIC colour scale
  • Crossflow elements without recess: free design options of the wall openings for builders and architects while maintaining the free cross-section ≥ 51 %
  • Nominal length and nominal heights selectable in mm steps


Nominal sizes

Nominal length LN:

  • 550 - 1175 mm in mm steps

Nominal height HN:

  • 290 - 440 mm in mm steps


Variants

CFE-..:

  • -*: in Z or T design
  • -*: with or without recess for diffuser face
  • -PP: Perforated sheet cover
  • -SC: Slot diffuser face


Construction

Surface finish of diffuser faces:

  • Powder-coated RAL 9010, pure white, GE 50
  • P1: powder-coated RAL 9006, white aluminium, GE 30
  • P1: powder-coated in other RAL CLASSIC colours, GE 70


Construction features

  • With or without recess for diffuser face
  • A diffuser face requires a construction with recess for the diffuser face
  • Nominal lengths from 550 - 1175 mm and nominal heights from 290 - 440 mm available in mm steps
  • The perforated sheet cover PP has a free cross-section of approx. 51 %, the hole diameter is 6 mm, and the rows of holes are arranged offset to each other
  • The slot diffuser face SC offers the largest possible free cross-section for very low pressure loss


Materials and surfaces

  • Casings and diffuser faces made of galvanised sheet steel
  • Acoustic lining made of mineral wool
  • Insulation strips on the casing made of closed cell PE foam
  • Diffuser faces powder-coated RAL9010, GE 50
  • P1: powder-coated colour according to RAL CLASSIC


 



Mineral wool:



  • Mineral wool on surfaces in contact with air are laminated with glass fibre fabric, abrasion-resistant up to 20 m/s
  • Acc. to EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous thanks to high biosolubility according to the German Ordinance on Hazardous Substances and Note Q of the European Regulation (EC) No 1272/2008
  • Inert to fungal and bacterial growth


Standards and guidelines

  • Sound power level of air-regenerated noise measured according to DIN EN ISO 5135
  • Conforms to VDI 6022
  • Sound reduction index according to DIN EN ISO 10140 and DIN EN ISO 717-1


Maintenance

  • Low maintenance, as there is no wear and tear due to design and materials used
  • Inspection and cleaning according to VDI 6022

Technical information

Function, Technical data, Quick sizing, Specification text, Order code

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
Schematic illustration, CFE-Z-PP CFE_Z_gc_14ai.png

1 Casing

2 Perforated sheet metal diffuser face

3 Sound insulation material made of mineral wool

4 Sealing strips

Type CFE crossflow elements can be installed in lightweight partition walls. Due to the pressure difference, the air flows e.g. from the office area as exhaust air into the hallway, into indoor zones or neighbouring areas with suspended ceilings. A central exhaust air system can be used there. Integrated acoustic lining reduces noise transmission into adjacent rooms. To avoid sound transmission on lightweight walls, insulation strips are attached to the casing for sound decoupling.

Nominal lengths

550 - 1175 in mm increments

Nominal height

290 - 440 in mm increments

maximum volume flow at ∆pt = 5 Pa, T-style construction, with slot cover

124 m³/h

maximum volume flow at ∆pt = 5 Pa, Z-style construction, with slot cover

120 m³/h

maximum volume flow at ∆pt = 10 Pa, T-style construction, with slot cover

175 m³/h

maximum volume flow at ∆pt = 10 Pa, Z-style construction, with slot cover

169 m³/h

Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures.

Exact values for all parameters can be determined with our Easy Product Finder design program.


Weighted sound reduction index, standard sound pressure level and sound power level, LN = 550, S = 0.019 m2

Variant

HN

Rw [dB]

Dn,e,w [dB]

∆pt = 5 Pa

∆pt = 10 Pa

qv [m³/h]

Lwa [dB(A)]

qv [m³/h]

Lwa [dB(A)]

CFE-T-SC29013.540.758<158216
CFE-T-SC3401643.257

<15

8015
CFE-T-SC44019.246.454<1577<15
CFE-T-PP29013.540.749<1570<15
CFE-T-PP34016.543.748<1568<15
CFE-T-PP44019.446.647<1566<15
CFE-Z-SC29013.440.656<157919
CFE-Z-SC34014.84255<157819
CFE-Z-SC44020.84853<157518
CFE-Z-PP29013.340.547<156617
CFE-Z-PP3401542.246<156517
CFE-Z-PP44020.84845<156316


Weighted sound reduction index, standard sound pressure level and sound power level, LN = 850, S = 0.030 m2

Variant

HN

Rw [dB]

Dn,e,w [dB]

∆pt = 5 Pa

∆pt = 10 Pa

qv [m³/h]

Lwa [dB(A)]

qv [m³/h]

Lwa [dB(A)]

CFE-T-SC29013.538.890

<15

12718
CFE-T-SC3401641.388<1512417
CFE-T-SC44019.244.584<1511916
CFE-T-PP29013.538.876<15108<15
CFE-T-PP34016.541.874<15105<15
CFE-T-PP44019.444.773<15103<15
CFE-Z-SC29013.438.787<1512321
CFE-Z-SC34014.840.185<1512121
CFE-Z-SC44020.846.182<1511619
CFE-Z-PP29013.338.672<1510219
CFE-Z-PP3401540.371<1510019
CFE-Z-PP44020.846.169<159818

 


 


Weighted sound reduction index, standard sound pressure level and sound power level, LN = 1000, S = 0.035 m2

Variant

HN

Rw [dB]

Dn,e,w [dB]

∆pt = 5 Pa

∆pt = 10 Pa

qv [m³/h]

Lwa [dB(A)]

qv [m³/h]

Lwa [dB(A)]

CFE-T-SC29013.538.1105

<15

14918
CFE-T-SC3401640.6103<1514618
CFE-T-SC44019.243.899<1514017
CFE-T-PP29013.538.190<1512715
CFE-T-PP34016.541.187<15124<15
CFE-T-PP44019.44485<15121<15
CFE-Z-SC29013.438102<1514422
CFE-Z-SC34014.839.4100<1514221
CFE-Z-SC44020.845.496<1513620
CFE-Z-PP29013.337.985<1512020
CFE-Z-PP3401539.683<1511719
CFE-Z-PP44020.845.481<1511519


Weighted sound reduction index, standard sound pressure level and sound power level, LN = 1175, S = 0.041 m2

Variant

HN

Rw [dB]

Dn,e,w [dB]

∆pt = 5 Pa

∆pt = 10 Pa

qv [m³/h]

Lwa [dB(A)]

qv [m³/h]

Lwa [dB(A)]

CFE-T-SC29013.537.4124

<15

17519
CFE-T-SC3401639.9121<1517118
CFE-T-SC44019.243.1116<1516417
CFE-T-PP29013.537.4105<1514916
CFE-T-PP34016.540.4103<1514515
CFE-T-PP44019.443.3100<15142<15
CFE-Z-SC29013.437.3120<1516922
CFE-Z-SC34014.838.7118<1516722
CFE-Z-SC44020.844.7113<1516021
CFE-Z-PP29013.337.2100<1514121
CFE-Z-PP3401538.998<1513820
CFE-Z-PP44020.844.795<1513519

Specification text

Crossflow elements with cross talk silencers are used for air transfer flow into adjacent rooms and are suitable for comfort areas.

The crossflow element is available in rectangular Z or T design. The nominal height and nominal length are variable within the limits in mm steps. Therefore, the crossflow element can be optimally adapted to project-specific requirements.

The design without recess for an air diffuser offers builders and architects, in compliance with the free cross section of 51%, various design options. For the version with recess for an air diffuser, a choice can be made between different diffuser fronts. The perforated diffuser face -PP has a free area of approx. 51%. The hole diameter is 6 mm, staggered pitch.

Fixing a diffuser face to the crossflow element after the drywalling has been completed is quick and easy.

The crossflow element includes a cross talk silencer with acoustic lining that reduces noise transmission to adjacent rooms. To prevent sound transmission via the casing, sealing strips are attached to the crossflow element.

Suitable for the space saving or concealed installation in lightweight partition walls with different stand widths.

Sound power level of the air-regenerated noise measured according to EN ISO 5135.

Sound reduction index according to DIN EN ISO 10140 and DIN EN ISO 717-1.

Crossflow element and diffuser face made of galvanised sheet steel.

Sound insulation material made of mineral wool.

Mineral wool:

  • Mineral wool on surfaces in contact with air are laminated with glass fibre fabric, abrasion-resistant up to 20 m/s
  • Acc. to EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous thanks to high biosolubility according to the German Ordinance on Hazardous Substances and Note Q of the European Regulation (EC) No 1272/2008
  • Inert to fungal and bacterial growth


Equivalence criteria

  • Different construction styles and sizes allow for meeting local and project-specific requirements
  • Low differential pressure
  • The crossflow element in Z-style construction without a recess for the diffuser face is suitable for thin lightweight partition walls with metal support structure
  • An integrated cross talk silencer reduces noise transmission into adjacent rooms.
  • Sealing strips on the casing minimise noise transmission
  • Diffuser face powder-coated in a RAL CLASSIC colour scale


Variants

Surface finish of diffuser faces:

  • Powder-coated RAL 9010, pure white, GU 50
  • P1: powder-coated RAL 9006, white aluminium, GU30
  • P1: powder-coated in other RAL CLASSIC colours, GU 70


Technical data

  • Nominal length: 550 to 1175 mm (in increments of 1 mm)
  • Nominal height: 290 to 440 mm (in increments of 1 mm)
  • Maximum volume flow rate ∆pt = 5 Pa: 124 m³/h
  • Maximum volume flow rate ∆pt = 10 Pa: 175 m³/h


Sizing data



  • LWA [dB(A)]


  • qv  [m³/h]
  • Δpt [Pa]
  • Dn, e, w [dB]
  • Rw [dB]






CFETSC/850 × 340/P1 - RAL 9016
|||||
12345
1 Type
CFE Crossflow element

2 Construction
Z
Z-style
T T-style

3 Air terminal device
No entry: without recess for diffuser face

With recess for diffuser face
PP Perforated metal diffuser faces
SC Slot diffuser faces
4 Nominal size [mm]
Nominal length × nominal height

Nominal length
550 – 1175

Nominal height
290 – 440 (standard height 340)

5 Diffuser face surface
No entry: powder-coated RAL 9010 (pure white)
P1 Powder-coated, specify RAL CLASSIC colour

Gloss level
RAL 9010 GU50
RAL 9006 GU30
All other RAL colours GU70


Order example: CFE-T-SC/850×300/P1-RAL9016

TypeCFE
ConstructionT-style
Air terminal deviceSlot diffuser faces
Nominal size [mm]Nominal length 850, nominal height 300
Diffuser face surfacePowder-coated RAL 9016 (traffic white)

Variants

  • VARIANTS


Downloads

product information

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34