Application
Parts and characteristics
Any attachments are to be defined with the order code of the multileaf damper.
Actuators for multileaf dampers
Z12 | M466DD6 | SM230A | – | – | 20 Nm | 100 – 240 V AC |
Z13 | M466DG3 | GM230A | – | – | 40 Nm | 100 – 240 V AC |
Z14 | M466DD5 | SM24A | – | – | 20 Nm | 24 V |
Z15 | M466DG1 | GM24A | – | – | 40 Nm | 24 V |
Z16 | M466DD6 | SM230A | M536AI3 | S2A | 20 Nm | 100 – 240 V AC |
Z17 | M466DG3 | GM230A | M536AI3 | S2A | 40 Nm | 100 – 240 V AC |
Z18 | M466DD5 | SM24A | M536AI3 | S2A | 20 Nm | 24 V |
Z19 | M466DG1 | GM24A | M536AI3 | S2A | 40 Nm | 24 V |
Z42 | M466DU4 | LM230A | – | – | 5 Nm | 100 – 240 V AC |
Z43 | M466EM8 | NM230A | – | – | 10 Nm | 100 – 240 V AC |
Z44 | M466DU5 | LM24A | – | – | 5 Nm | 24 V |
Z45 | M466EM9 | NM24A | – | – | 10 Nm | 24 V |
Z46 | M466DU4 | LM230A | M536AI3 | S2A | 5 Nm | 100 – 240 V AC |
Z47 | M466EM8 | NM230A | M536AI3 | S2A | 10 Nm | 100 – 240 V AC |
Z48 | M466DU5 | LM24A | M536AI3 | S2A | 5 Nm | 24 V |
Z49 | M466EM9 | NM24A | M536AI3 | S2A | 10 Nm | 24 V |
Fast-running actuators for multileaf dampers
ZS21 | M466EU4 | SMQ24A | – | – | 16 Nm | 24 V |
ZS22 | M466EU4 | SMQ24A | M536AI3 | S2A | 16 Nm | 24 V |
Application
Variants
Parts and characteristics
Actuator SM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC −10 %, +20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.0 kg |
Actuator GM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 40 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (open/close) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.7 kg |
Actuators LM24A and LM24A-F
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power consumption – load | 1 W |
Power consumption – idle | 0.2 W |
Power rating | 1.5 VA |
Torque | 5 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Actuator NM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±20 % |
Power rating (AC) | 3.5 VA max. |
Power rating (DC) | 1.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.75 kg |
Fast-running actuator SMQ24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC −10 %, +20 % |
Power rating (AC) | 26 VA max. |
Power rating (DC) | 15 W max. |
Torque | 16 Nm |
Running time for 90° | 7 s |
Control input signal | 1-wire control |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 40 °C |
Weight | 1.7 kg |
Application
Variants
Parts and characteristics
Actuator SM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 6 VA max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.0 kg |
Actuator GM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 9 VA max. |
Torque | 40 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (open/close) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.7 kg |
Actuator LM230A and LM230A-F
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power consumption – load | 1.5 W |
Power consumption – idle | 0.5 W |
Power rating | 3.5 VA |
Torque | 5 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Actuator NM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 5.5 VA max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.75 kg |
Application
Auxiliary switch S2A
Type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.250 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34
Contact
We are here for you
Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34