EK-JZ smoke control dampers with ventilation function for heat and smoke exhaust

img_pro_TLT00101.png
BVDAX for smoke extract in combination with a frequency inverter

BVDAX for smoke extraction

operation with frequency

converter, CE certified in accordance with EN 12101-3

Temperature category F400

img_pro_003742.jpg
For mechanical smoke extract systems and pressure differential systems

For mechanical smoke extract systems and pressure differential systems

img_pro_003602.png
Maximum performance with maximum size B = 1.20 m, H = 2.03 m

Maximum size, maximum performance

B = 1.20 m, H = 2.03 m

img_pro_003604.png
Minimum leakage with both high and low temperatures due to 2-component sealing system

Minimum leakage with both high and low temperatures due to 2-component sealing system

 

EK-JZ_img_25ai.png
Vertical installation position

Vertical damper blade alignment possible

EK-JZ_img_19psd.png
img_pro_TLT00101.png
img_pro_003742.jpg
img_pro_003602.png
img_pro_003604.png
EK-JZ_img_25ai.png

EK-JZ

FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND PRESSURE DIFFERENTIAL SYSTEMS, AS WELL AS FOR PROVIDING ADDITIONAL SUPPLY AIR

Rectangular smoke control dampers with ventilation function, low installation depth and large cross section for heat and smoke exhaust with mechanical smoke extract systems, for the provision of additional supply air and for use in pressure differential systems

  • Nominal sizes 200 × 230 – 1200 × 2030 mm, for smoke gas flow rates up to 29230 m³/h or 105235 m³/h at 12 m/s, upstream velocities up to 20 m/s possible 
  • Simple and quick installation in and on components
  • Casing, damper blades and actuator encasing made of calcium silicate
  • Pressure level 2 (operating pressure -1000 to 500 Pa)
  • Automatic release (AA), option of manual override (MA)
  • For smoke extract ducts from 35 mm wall thickness
  • Closed blade air leakage to EN 1751, class 3
  • Casing air leakage to EN 1751, class C


Optional equipment and accessories

  • Cover grille (various constructions)
  • Connecting subframe for calcium silicate and sheet steel smoke extract ducts
  • Integration into the central BMS with TROXNETCOM
  • Coating for use in exterior walls
  • Cmod = for smoke extract and ventilation in combined systems, which allows for pneumatic volume flow rate balancing as the damper blade can take intermediate positions
  • Installation accessories

Updating order code
Save configuration
Calculate price
Updating technical data
  • Media
Specification text:
Updating specification text
Show complete text Hide complete text
Initialize order code

General information

Application

  • Smoke control damper, with CE marking and declaration of performance, for heat and smoke exhaust with mechanical smoke extract systems
  • Can be used for the provision of fresh air (additional supply air) to mechanical smoke extract systems
  • Can be used in pressure differential systems
  • Can be used for ventilation if the mechanical smoke extract system has been certified (general building inspectorate licence) for use with combined systems
  • Integration into the central BMS with TROXNETCOM


Special features

  • Cmod for smoke extract and ventilation in combined systems, which allows for pneumatic volume flow rate balancing as the damper blade can take intermediate positions 
  • Complies with the requirements of EN 12101-8
  • Tested to EN 1366-2 and 1366-10 for fire resistance properties
  • Closed blade air leakage to EN 1751, Class 3, and casing leakage to EN 1751, Class C
  • Low sound power level and differential pressure
  • Any airflow direction
  • Manual release is also possible using TROXNETCOM
  • Long-time testing to EN 1366-10, with 20000 OPEN/CLOSE cycles


Classification

EI 120/90 (vedw-hodw, i↔o) S1000 Cmod HOT 400/30 MA multi


Nominal sizes

  • 200 × 230 – 1200 × 2030 mm
  • Casing lengths L = 250 mm


Parts and characteristics

  • Installation orientation is independent of the airflow direction
  • Pressure level 2 (operating pressure -1000 to 500 Pa)
  • For automatic and manual release
  • Smoke control damper with ventilation function


Attachments 1

  • Connecting subframe for calcium silicate and sheet steel smoke extract ducts
  • Cover grille – crimped wire mesh or square perforated metal plate
  • Cover grille – grille with straight or slanted blades


Attachments 2

  • Open/Close actuators with 24 V AC/DC or 230 V AC supply voltage
  • Network modules for the integration with AS-i networks
  • Network modules for other standard bus systems


Optional products

TROXNETCOM

  • X-FANS control unit for extract air and smoke extract control

 

TROX-X smoke exhaust fans from the X-FANS subassembly

  • Smoke exhaust fan for roof installation BVDAX/ BVD
  • Smoke exhaust fan for wall installation BVW/ BVWAXN
  • Smoke exhaust centrifugal fan BVREH /BVRA
  • Smoke extract jet fans BVGAX/BVGAXN

 

All smoke exhaust fans are tested to ​EN 12101-3, for F200/F300/​F400 and F600, depending on the type. With CE marking, declaration of performance and application approval for the German market.

    Speed adjustment for smoke exhaust fans

    • Certified frequency inverter unit X-FANS control
    • Safe and precise speed adjustment of smoke exhaust fans both in one-zone and in multi-zone systems.


    Construction features

    • Rectangular construction
    • Smoke control damper actuator controlled by reversible open/close actuator
    • Remote control with actuator
    • Suitable for the connection of cover grilles or connecting subframes


    Materials and surfaces

    • Casing, damper blade and actuator encasing made of calcium silicate
    • Brass bearings
    • Blade shafts, drive arm and shaft bearing made of galvanised steel


    Standards and guidelines

    • Construction Products Regulation
    • EN 12101-8 Smoke and heat control systems – Smoke control dampers
    • EN 1366-10 Fire resistance tests for service installations – Smoke control dampers
    • EN 1366-2 Fire resistance tests for service installations – Fire dampers
    • EN 13501-4 Fire classification of construction products and building elements using data from fire resistance tests
    • EN 1751 Ventilation for buildings – Air terminal devices


    Maintenance

    Smoke control dampers must be operational at all times and must be maintained regularly so that they provide the required services.

    • Maintenance is required at least every 6 months
    • A maintenance report must be created; documents must be kept for reference
    • The functional reliability of the smoke control damper must be tested at least every six months; this has to be arranged by the owner of the smoke extract system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later
    • Depending on where dampers are installed, country-specific regulations may apply.
    • For details on maintenance and inspection, refer to the installation and operating manual.

Technical information

Function, Technical Data, Quick sizing, Specification text, Order code

  • Function
  • TECHNICAL DATA
  • QUICK SIZING SUITABLE FOR INSTALLATION TYPE
  • SPECIFICATION TEXT
  • ORDER CODE
Schematic illustration EK-JZ_gc_01ai.png

① Casing

② Blades

③ Blade tip seal (special profile seal)

④ Side seal

⑤ Travel stop, bottom

⑥ Actuator

⑦ Cover fixing

⑧ Rating plate

⑨ Cover of the actuator encasing

⑩ Handle (to remove the cover)

⑪ Actuator encasing

⑫ Travel stop, top

Smoke control dampers are used in mechanical smoke extract systems. They are used for extracting smoke gases and for providing additional supply air to one or more fire compartments. The dampers are made of calcium silicate panels and are opened by an encased actuator; when smoke is detected, the actuator is triggered by a signal either from a duct smoke detector or from a fire alarm system. Smoke control dampers have two safe positions: open and closed. In the case of fire-resistant smoke control dampers for multiple compartments, the safe position is either "open" or "closed", depending on the fire site and the path of the smoke to be extracted. If the safe position is 'open', the free area must be maintained even in the event of a fire. The blades of EK-JZ move to the defined safe position upon receiving an automatically or manually triggered control signal. According to the specified time-temperature curve, the EK-JZ can still fully open or close after 25 minutes (MA, manual release). With the EK-JZ product type, it is also possible to change the position for modulation uses (Cmod) and thus a pneumatic adjustment in the ventilation operation of a combined system by moving to intermediate positions of the damper blade field. Regular maintenance of the smoke control damper is required to ensure its functional reliability.

Nominal sizes B × H200 × 230 mm – 1200 × 2030 mm
Casing length [mm]250 mm
Flow rate range at maximum upstream velocityUp to 920 l/s or up to 3310 m³/h – up to 29230 l/s or up to 105235 m³/h
Differential pressure rangePressure level 2: -1000 – 500 Pa
Operating temperatureAt least -30 to 50 °C; the temperature should not fall below the dew point
Upstream velocity*Up to 12 m/s for maximum dimension and ≤ 20 m/s for damper sizes up to 1200 × 1830 mm, otherwise technical clarification required

* Data applies to uniform upstream and downstream conditions for the smoke control damper


  • Quick sizing tables in Easy Product Finder provide a good overview of the volume flow rates for different airflow velocities as well as of differential pressures
  • Precise values based on project-specific data can be determined with our Easy Product Finder design software
  • You will find the Easy Product Finder on our website 
    www.trox.de/mytrox/auslegungsprogramm-easy-poduct-finder-182e16348fac3d33

Rectangular or square smoke control dampers to product standard EN 12101-8, tested to EN 1366-10 and EN 1366-2, for use in smoke extract systems. Smoke control dampers are not only used for the exhaust of smoke, heat and combustion products from a fire compartment, but also for the controlled removal of dangerous and toxic combustion and fire suppression gases. EK-JZ smoke control dampers can also be used in pressure differential systems and as pressure relief dampers in gas fire extinguishing systems. Also for extracting smoke gases and for providing additional supply air for the mechanical smoke extract of one or more fire compartments and in all listed systems of the same type that need to fulfil modulation applications. EK-JZ can be used in combined smoke exhaust systems which have been approved for controlled ventilation. The fire-resistant smoke control damper for multiple compartments is suitable for installation in and on fire-resistant smoke extract ducts or smoke extract shafts and in fire-resistant standard supporting constructions. The control of open/close actuators can be implemented with control modules that are factory wired or with bus modules inside the temperature-resistant actuator encasing.

Classification

EI 120/90 (vedw-hodw, i↔o) S1000 Cmod HOT 400/30 MA multi

Special features

  • Cmod for smoke extract and ventilation in combined systems, which allows for pneumatic volume flow rate balancing as the damper blade can take intermediate positions 
  • Complies with the requirements of EN 12101-8
  • Tested to EN 1366-2 and 1366-10 for fire resistance properties
  • Closed blade air leakage to EN 1751, Class 3, and casing leakage to EN 1751, Class C
  • Low sound power level and differential pressure
  • Any airflow direction
  • Manual release is also possible using TROXNETCOM
  • Long-time testing to EN 1366-10, with 20000 OPEN/CLOSE cycles


Materials and surfaces

  • Casing, damper blade and actuator encasing made of calcium silicate
  • Brass bearings
  • Blade shafts, drive arm and shaft bearing made of galvanised steel


Technical data

  • Nominal sizes B × H: 200 × 230 mm – 1200 × 2030 mm
  • Casing length: 250 mm
  • Volume flow rate at maximum dimension: up to 29230 l/s or up to 105235 m³/h (after technical clarification, up to 48720 l/s or up to 175390 m³/h possible)
  • Differential pressure range: pressure level 2: -1000 – 500 Pa
  • Operating temperature: -30 °C to 50 °C; the temperature should not fall below the dew point
  • Upstream velocities*: up to 12 m/s for maximum dimension and ≤ 20 m/s for damper sizes up to 1200 × 1830 mm, otherwise technical clarification required
     

* Technical data applies to uniform upstream and downstream conditions for the smoke control damper


Attachments

Connecting subframe and cover grille for the operating side and/or installation side.

  • Connecting subframe for calcium silicate and sheet steel smoke extract ducts
  • Cover grille – crimped wire mesh or square perforated metal plate
  • Cover grille – external weather louvre or ventilation grille

 

Open/close actuators for the control of smoke control dampers, with automatic (AA) or manual release (MA).

Optional control or communication module for integration with the central BMS.

  • Supply voltage 24 V AC/DC or 230 V AC
  • Limit switches for capturing the end positions OPEN and CLOSED
  • Override control for up to 25 minutes
  • Module for the control of smoke control dampers (optional)
  • Indicator lights for indicating the damper blade position
  • Monitoring of signal reception

Sizing data

qᵥ [m³/h]

Δpst [Pa]

Air-regenerated noise

LPA [dB(A)]

EK-JZRVC1 / DE / 1200 × 2030 / 13 / FA / B24A / P1 - RAL...
||||||||||
12345678910

1 Type
EK-JZ 

Smoke control damper according to EN 12101-8

2 Enclosure As seen from the operating side
R On the right (as standard)
L Left

3 Damper blade alignment
No entry required: Horizontal damper blade alignment (standard)
V Vertical damper blade alignment 

4 Coating
No entry required: None (standard)
C1 PROMAT SR impregnation

5 Country of destination
DE Germany
CH Switzerland
AT Austria
PL Poland
and others

6 Nominal size
[mm]
B × H (B in 50 mm increments; H in 200 mm increments)
From 200 × 230 to 1200 × 2030

7 Accessories 1 
No entry required = None (standard)
01 Fixing tabs (quantity depends on B x H)
Only in the case of horizontal damper blade alignment
02 Lower HT seal
03 Lower HT seal and fixing tabs (quantity depends on B x H)
04 Side HT seal
05 Lower and side HT seals
06 Lower and side HT seals and fixing tabs (quantity depends on B x H)
07 Side HT seal and fixing tabs (quantity depends on B x H)
08 Upper (special) HT seal
09 Upper (special) and side HT seals
10 Upper (special) HT seal and fixing tabs (quantity depends on B x H) 
11 Upper (special) and side HT seals and fixing tabs (quantity depends on B x H)
12 Ceiling fixing tabs (double quantity depends on B x H)

Only in the case of vertical damper blade alignment
13 Upper (special) HT seal
14 Upper (special) and side HT seals
15 Upper (special) HT seal and fixing tabs (quantity depends on B x H)
16 Upper (special) and side HT seals and fixing tabs (quantity depends on B x H)

8 Attachments 1
No entry required: None
F Connecting subframe, galvanised steel, cover grille
A Crimped wire mesh, 20 × 20, galvanised steel
B Square perforated metal plate, 10 × 10, galvanised steel
C Grille with slanted blades made of aluminium
D Grille with slanted blades, aluminium, additionally with crimped wire mesh, 20 × 20, galvanised steel
E Grille with slanted blades, aluminium, additionally with welded wire mesh, 6 × 6 mm, galvanised steel

Character 1 refers to the operating side,, without attachment on operating side: 0
Character 2 defines installation side, without attachment on installation side: 0
Example: FA: Connecting subframe on the operating side, crimped wire mesh 20 × 20 on the installation side
Any combination is possible

9 Attachments 2
Actuator
B24  Actuator, Belimo, 24 V AC/DC
B24SR Actuator, Belimo, 24 V AC/DC, continuous control with operating range of 2 - 10 V DC, ventilation function Cmod1
B230 Actuator, Belimo, 230 V AC
Actuator combined with TROX control moduleB24A Actuator, Belimo, 24 V AC/DC with TROXNETCOM control module AS-EM/EK 2
B24AS Actuator, Belimo, 24 V AC/DC with TROXNETCOM control module AS-EM/SIL2, 2
B24AM Actuator, Belimo, 24 V AC/DC with TROXNETCOM control module AS-EM/M, for function Cmod1

Other communication modules:
B24BKNE Actuator, Belimo, 24 V AC/DC, Belimo communication and power supply unit BKNE230-24
B24C Actuator, Belimo, 24 V AC/DC, BV-Control communication and power supply unit with SLC® technology BC24 G2)
B24D Actuator Belimo, 24 V AC/DC, Agnosys fire damper smoke control damper module BRM-10-F-ST
B230D Actuator Belimo, 230 V AC, Agnosys fire damper and smoke control damper module BRM-10-F

1 Function Cmod for damper blade in intermediate position
2 The AS-i system is based on the industrial standard AS-Interface
 10 Surface finish (attachments 1)
No entry required: None (standard)
P1 Powder-coated, specify RAL CLASSIC colour
PS Powder-coated, specify DB colour Gloss level:
RAL 9010 50 %
RAL 9006 30 %
All other RAL colours 70 %


Order example: EK-JZ-R-V-C1/DE/800 × 1030/14/A0/B24A/P1-RAL9010-50%
Actuator encasingOperating side, on the right
Damper blade alignmentVertical
CoatingImpregnation
Country of destinationGermany
Nominal size800 × 1030 mm
Accessories 1Side and upper (special) HT seals
Attachment 1Cover grille on the operating side
Attachment 2TROX actuator Belimo, with TROXNETCOM control module AS-EM/EK
Surface attachmentP1-RAL9010 50 % cover grille with powder coating, RAL 9010, pure white, gloss level 50 %

Dimensions and weight

  • DIMENSIONS AND WEIGHT
Dimensions EK-JZ Dimensions EK-JZ

a Installation side
b Operating side
① Subframe for connection to the duct (steel, operating side only and or installation side, optional)
② Keep clear to provide access to the actuator encasing

Weights [kg], width 200 – 650 mm

LHB
200250300350400450500550600650
25023021222324252728293031
25043029313233353638394142
25063037394143444648505153
25083046485053545658616264
250103054565961636668707375
250123062656770737578818386
250143071737679828588919497
250163079828588929598101105108
250183087919498101105108112115119
25020309599103107111114118122126130

Weights [kg], width 700 – 1200 mm
LHB
70075080085090095010001050110011501200
2502303234353637383940424344
2504304445474849515254555758
2506305557586062646567697172
2508306669707275777880838587
250103077808284878991949698101
25012308991949799102104107110112115
2501430100103106109112115117120123126129
2501630111114118121124127130134137140143
2501830122126129133136140143147150154158
2502030134137141145149153156160164168172

Accessories, Attachments 1&2, Wiring examples & technical data , Building Management System (BMS)

  • ACCESSORIES
  •  ATTACHMENTS 1&2
  • WIRING EXAMPLES & TECHNICAL DATA
  • BUILDING MANAGEMENT SYSTEM (BMS)


No entry required = None (standard)
01 Fixing tabs (quantity depends on B x H)

Only in the case of horizontal damper blade alignment
02 Lower HT seal
03 Lower HT seal and fixing tabs (quantity depends on B x H)
04 Side HT seal
05 Lower and side HT seals
06 Lower and side HT seals and fixing tabs (quantity depends on B x H)
07 Side HT seal and fixing tabs (quantity depends on B x H)
08 Upper (special) HT seal
09 Upper (special) and side HT seals
10 Upper (special) HT seal and fixing tabs (quantity depends on B x H) 
11 Upper (special) and side HT seals and fixing tabs (quantity depends on B x H)
12 Ceiling fixing tabs (double quantity depends on B x H)

Only in the case of vertical damper blade alignment
13 Upper (special) HT seal
14 Side and upper (special) HT seals
15 Upper (special) HT seal and fixing tabs (quantity depends on B x H)
16 Upper (special) and side HT seals and fixing tabs (quantity depends on B x H) 



ATTACHMENTS 1

F, A, B, C, D, E – Connecting subframes and cover grilles

Application

  • A connecting subframe (F) is required for sheet steel smoke extract ducts Cover grilles are attached to the damper or to the end of ducts; this application has been approved based on a fire test to EN 1366-10
  • The cover grille free area is approx. 80 % for crimped wire mesh (A) and approx. 70 % for perforated metal plates
  • Cover grille variants C, D, E cover the section of blades of the EK-JZ but not the actuator encasing
  • If you order a cover grille separately, you may choose a size that covers the damper blades and the actuator encasing and fix the grille along the perimeter of the shaft wall
  • Connecting subframes are factory mounted and form a unit
  • Connecting subframes and cover grilles may also be ordered separately
  • The cover grill and accessories are supplied separately


Materials and surfaces 

  • F: Connecting subframe made of galvanised sheet steel

Cover grilles

  • A: Crimped wire mesh made of galvanised steel
  • B: Perforated metal plate made of galvanised sheet steel
  • C: Grille with slanted blades made of aluminium
  • D: Grille with slanted blades made of aluminium, crimped wire mesh made of galvanised steel
  • E: Grille with slanted blades made of aluminium, welded wire mesh made of galvanised steel
  • All attachments can be powder-coated


Connecting subframes and cover grilles

Operating sideInstallation sideOrder code
Connecting subframeF0
Connecting subframe0F
Connecting subframeConnecting subframeFF
Cover grille AA0
Cover grille A0A
Cover grille ACover grille AAA
Cover grille BB0 
Cover grille B0B
Cover grille BCover grille BBB
Cover grille CC0
Cover grille C0C
Cover grille CCover grille CCC
Cover grille DD0
Cover grille D0D
Cover grille DCover grille DDD
Cover grille EE0 
Cover grille E0E
Cover grille ECover grille EEE

A: Crimped wire mesh, 20 × 20 × 1.8 mm, galvanised steel (AG-E)
B: Square perforated metal plate, 10 × 10 mm, galvanised steel (AG-E)
C: Grille with slanted blades, aluminium (ALG-E)
D: Grille with slanted blades, aluminium, additionally with crimped wire mesh, 20 × 20 x 1.8 mm, galvanised steel (ALG-E)
E: Grille with slanted blades, aluminium, additionally with welded wire mesh, 6 × 6 mm, galvanised steel (ALG-E)
Any combination is possible


Attachments 2


Application

  • Open/close actuators for the opening and closure of smoke control dampers, with automatic (AA) or manual release (MA).
  • With integral limit switches for capturing the end positions
  • Override control for up to 25 minutes
  • Ambient temperature for normal operation: -30 to 50 °C, up to 95%, without temperatures below the dew point, no condensation (EN 60730-1)
  • Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
  • The connecting cables of the 24 V actuator are fitted with plugs, which ensure quick and easy connection to the TROX AS-i bus system
  • The connecting cable of the 230 V AC actuator is fitted with wire end ferrules


Variants

B24

  • 24 V AC/DC supply voltage
  • BEN24-ST TR: Torque 15 Nm
  • BEE24-ST TR: Torque 25 Nm
  • BE24-12-ST TR: Torque 40 Nm
     

B230

  • Supply voltage 230 V AC
  • BEN230 TR: Torque 15 Nm
  • BEE230 TR: Torque 25 Nm
  • BE230-12 TR: Torque 40 Nm
     

B24-SR

  • BEN24-SR: Torque 15 Nm
  • BEE24-SR: Torque 25 Nm
     

The torque required to operate the smoke control damper depends on the size which is why the actuator type cannot be chosen freely.

Installation information

  • Feeding the electric connecting cable through the actuator encasing requires a drilled hole of the exact size (Ø max. + 1 mm)
  • A wire clamping bracket is required
  • For details on maintenance and inspection, refer to the installation and operating manual.

Wiring example 24 V AC / DC

ActuatorBEN24-STBEE24-STBE24-ST
Supply voltage (AC)AC 19.2 – 28.8 V, 50/60 Hz
Supply voltage (DC)DC 21.6 – 28.8 V, 50/60 Hz

Power consumption – when running

3 W2.5 W

12 W

Power consumption – when idle

0.1 W

0.5 W

Power rating for cable sizing

Imax. 8.2 A at 5 ms
Torque15 Nm25 Nm

40 Nm

Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V1 mA – 6 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°87°
Connecting cable – actuatorCable 1 m, 3 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classIII safety extra low voltage (SELV)
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C
Weight0.9 kg1.1 kg

2.7 kg




Wiring example 230 V AC

ActuatorBEN230 TRBEE230 TRBE230 TR
Supply voltage (AC)AC 198 – 264 V, 50/60 Hz

Power consumption – when running

4 W3.5 W

8 W

Power consumption – when idle

0.4 W0.5 W

Power rating for cable sizing

Imax. 4 A at 5 msImax. 7.9 A at 5 ms
Torque15 Nm25 Nm

40 Nm

Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V1 mA – 6 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°87°
Connecting cable – actuatorCable 1 m, 3 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classII reinforced insulation
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C-30 to 50 °C
Weight0.9 kg1.1 kg

2.7 kg



WIRING EXAMPLE 24 V AC / DC

ActuatorBEN24-SRBEE24-SR
Supply voltage (AC)AC 19.2 – 28.8 V, 50/60 Hz
Supply voltage (DC)DC 21.6 – 28.8 V, 50/60 Hz

Power consumption – when running

3 W

Power consumption – when idle

0.3 W

Power rating for cable sizing

Imax. 8.2 A at 5 ms
Torque15 Nm25 Nm
Run time for 90°

< 30 s

Limit switch contacts

2 × EPU
Switching current1 mA – 3 A (0.5 A inductive), AC 250 V
Limit switch – open
Limit switch – close80°
Connecting cable – actuatorCable 1 m, 4 × 0.75 mm², halogen-free

Connecting cable – limit switches

Cable 1 m, 6 × 0.75 mm², halogen-free
IEC protection classIII safety extra low voltage (SELV)
Protection level

IP 54

EC conformityCE according to 2014/30/EU
Low Voltage Directive CE according to 2014/35/EU
Operating temperature-30 to 55 °C
Weight1.1 kg0.9 kg


Interfaces to higher level systems

TROX fire and smoke protection systems have standardised interfaces for central building management systems. In the simplest case, the interface consists of discrete signalling contacts that connect the alternating inputs and outputs of TROX systems and other building components.


Control and communication modules for smoke control dampers

Order characteristicB24AB24ASB24AMB24BKNEB24CB230DB24D
Module type

AS-EM/EK

AS-EM/SIL2

AS-EM/MBKNE230-24BC24BRM-10-FBRM-10-F-ST
EK2-EU

×

×

×

×

×

×

×

EK-JZ

×

×

×

×

×

×

×


Note:
The smoke control dampers, actuators and communication modules described have each been verified by the manufacturer as a unit in terms of fire protection and may therefore only be used in such constellations.


B24A – AS-EM/EK

Application


  • Module for the control of smoke control dampers
  • Capturing damper blade positions OPEN and CLOSED
  • Actuators can be started even without controller communication
  • LEDs for OPEN and CLOSED positions; monitoring of run time errors
  • Integral AS-Interface slave
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator
  • Supply voltage of the module and the 24 V DC actuator using AS-Interface ( 2-wire control)
  • Plug-in connection for Belimo actuators (factory-mounted and wired)


Use

B24A – Mounted to the smoke control damper

Description

AS-EM/EK

Electrical design

4 inputs/3 outputs

Output function

PNP transistor

Supply voltage

26.5 – 31.6 V DC

Current consumption, including actuator

450 mA



Inputs:


Switching

DC PNP

Sensor voltage supply

AS-i

Voltage range

18 – 30 V AC

With short circuit protection

Yes

Switching level – high signal 1

10

Input current high/low

> 7 mA/< 2 mA

Input characteristic

IEC 61131-2 Type 2



Outputs, PNP:


Galvanically isolated

No

Max. current load per output

400 mA per output/400 in total (from AS-i)


Outputs, relay:


Galvanically isolated

Yes

Maximum voltage

32 V

Max. current load

500 mA

Ambient temperature

-5 to 75 °C

Protection level, IEC protection class

IP 42

AS-i profile

S-7.A.E

I/O configuration

7 Hex

ID code

7 Hex

EMC

EN 61000-6-2; EN 61000-6-3



B24AS – AS-EM/SIL2

Application


  • Module for the control of smoke control dampers
  • Capturing damper blade positions OPEN and CLOSED
  • Approved up to SIL2 to IEC/EN 61508
  • Integrated AS-Interface
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator
  • Connection with terminals
  • Supply voltage of the module and the 24 V DC actuator using AS-Interface (2-wire control)
  • Plug-in connection for Belimo actuators (factory-mounted and wired)


Use

B24AS – Mounted to the smoke control damper

Description

AS-EM/SIL2

Supply voltage

26.5 – 31.6 V DC

Current consumption

< 400 mA from AS-i

Max. current load per output

340 mA

Max. current load per module

340 mA

Status LED

AS-i power

1 × green

PeripheralFault

1 × red, blinking

ComError

1 × red, static

Output Q0

1 × yellow (DO0)

Output Q1

1 × yellow (DO1)

Input status LED SI-1

1 × yellow

Input status LED SI-2

1 × yellow

Input status DI0

1 × yellow (DI0)

Input status DI1

1 × yellow (DI1)

Input status DI2

1 × yellow (DI2)

Binary inputs

2 outputs with transistor (typically 24 V DC from AS-i, voltage range 18 – 30 V)

Operating temperature

-20 to 70 °C

Storage temperature

-20 to 75 °C

Protection level, IEC protection class

IP 54

Casing material

Plastic

AS-i profile

S-7.B.E (Safety at Work) and S7.A.E (motor module)

EMC

EN 61000-6-2; EN 61000-6-3



B24AM – AS-EM/M

Application

  • Module for the control of smoke control dampers with Cmod function:
  • Capturing the damper blade end positions (CLOSED and OPEN)
  • Time-controlled selection of 13 intermediate positions of the damper blade (opening angle between 0° and 90°) 
  • Actuators can be started even without controller communication
  • Emergency position can be set (OPEN or CLOSED)
  • LEDs for OPEN and CLOSED positions; monitoring of run time errors
  • Integral AS-Interface slave
  • Monitoring of signal reception
  • Master can be used to monitor the run time of the damper blade actuator 
  • Supply voltage of the module and 24 V DC actuator using AS-Interface (2-wire control)
  • Plug-in connection for Belimo actuators


Use

B24AM – Mounted to the smoke control damper

DescriptionAS-EM/M

Electrical design

4 inputs/3 outputs

Output function

PNP transistor

Supply voltage

26.5 – 31.6 V DC

Current consumption, including actuator

450 mA

Inputs

Switching

DC PNP

Sensor voltage supply

AS-i

Voltage range

18 – 30 V AC

With short circuit protection

Yes

Switching level – high signal 1

10

Input current high/low

> 7 mA/< 2 mA

Input characteristic

IEC 61131-2 Type 2

Outputs, PNP

Galvanically isolated

No

Max. current load per output

400 mA per output/400 in total (from AS-i)

Outputs, relay

Galvanically isolated

Yes

Maximum voltage

32 V

Max. current load

500 mA

Ambient temperature

-5 to 75 °C

Protection level, IEC protection class

IP 42

AS-i profile

S-7.A.E

I/O configuration

7 Hex

ID code

7 Hex

EMC

EN 61000-6-2; EN 61000-6-3



B24BKNE – Communication module

Application

  • Communication and power supply unit for 24 V actuators in smoke extract applications, status LEDs, retention of the damper control input signal, 230 V AC connection, 1 m cable, free of halogens


Use

B24BKNE – BKNE230-24 communication module

DescriptionBKNE230-24

Nominal voltage

230 V AC 50/60 Hz

Functional range

198 – 264 V AC

Rating

19 VA (including actuator)

Power consumption

10 W (including actuator)

Length / cross section

On the actuator = 1 m, 3 (6*) × 0.75 mm² (free of halogens)

IEC protection class

II (protective insulation)

Ambient temperature

-30 to 50 °C

Storage temperature

-40 to 80 °C

Protection level

IP 54

EC conformity

EMC to 89/336/EEC, 73/23/EEC

Mode of action

Type 1 (EN60730-1)

Software class

A (EN60730-1)

Maintenance

Maintenance-free

Weight

680 g



B24C – Communication module

Application

  • SLC® technology
  • The BC 24 module is used for the control of damper actuators
  • Power supply and communication are implemented with an interchangeable two-core cable, SLC24-16B system.
  • A thermoelectric release mechanism and a duct smoke detector can be connected without the need for additional devices


Use

B24C – BC24-G2 communication module from BV-Control AG

DescriptionB24C

Nominal voltage

From SLC® control module

Power consumption

1 W

Connections

Plug connections, screw terminals

Damper power supply

24 V

Ambient temperature

-20 to 50 °C

Storage temperature

-20 to 80 °C

Humidity

95 % rh, no condensation

Weight

255 g

B × H × T

114 × 153 × 54 mm

Max. impulse voltage

2.5 kV (EN60730-1)



B24D, B230D – Communication module

Application

  • AGNOSYS system
  • BRM-F-ST module is used for the monitoring and control of smoke control dampers 
  • Up to 126 modules can be connected in a ring topology


Use

B24D – AGNOSYS BRM10FST communication module
B230D – AGNOSYS BRM10F communication module

DescriptionB24D/B230D

Nominal voltage

18 – 32 V DC (typically 24 V)

Connections

Plug connections, screw terminals

Damper power supply

24/230 V AC 24 V DC

Ambient temperature

0 to 45 °C

Humidity

90 % rh, no condensation

Weight

510 g

B × H × T

158 × 180 × 65 mm

Downloads

product information

brochures

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://*.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://*.onventis.com http://localhost:63342 http://cerebrum.local https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34

Contact

We are here for you

Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34