Set flow rates
Application
With heavy dust levels in the room
If the air is contaminated with fluff, sticky components or aggressive substances
Construction
Parts and characteristics
Interface
Control strategy
Operating modes
Commissioning
A closed control circuit for regulation of the volume flow rate, i.e. measuring - comparing - adjusting, is characteristic of air terminal units.
The volume flow rate is measured by measuring a differential pressure (effective pressure). This is done via a differential pressure sensor. An integrated differential pressure transducer converts the effective pressure into a voltage signal. The volume flow rate actual value is hence available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal volume flow rate (qvnom).
The volume flow rate setpoint value comes from a higher-level controller (e.g. room temperature controller, air quality controller, central BMS) or from switch contacts. Variable volume flow control results in a value between qvmin and qvmax. It is possible to override the room temperature control, e.g. by a complete shut-off of the duct.
The controller compares the volume flow rate setpoint value to the actual value and controls the integral actuator accordingly.
Flow rate parameter qvmin and qvmax can be set on potentiometers.
Category
Type Easy volume flow rate controller with potentiometers to set qvmin, qvmax
Application
Area of application
Actuator
Installation orientation
Connection
Supply voltage
Interface/signalling
Interface information
Special functions
Parameter setting
Factory condition
TVR | – | D | / | 200 | / | D2 | / | Easy |
| | | | | | | | | | ||||
1 | 2 | 5 | 6 | 7 |
2 Acoustic cladding
D With acoustic cladding
3 Material
5 Nominal size [mm]
100
125
160
200
250
315
400
6 Accessories
No entry: none
D2 Lip seals on both ends
G2 Matching flanges for both ends
7 Attachments (control components)
Easy Easy controller
Acoustic cladding | With |
Material | Galvanised sheet steel |
Nominal size | 125 mm |
Accessories | Double lip seal both ends |
Attachment | Easy controller |
Commissioning
Description of status LEDs and error messages regarding control components for terminal unit TVE
LED pushbutton flashing signal | Flashing signal in words | Status |
---|---|---|
LED off | No voltage | |
LED blinks 4 times briefly within 2 seconds. | Call the TROX Technical Service | |
LED blinks 3 times briefly within 2 seconds. | Actuator overload detected | |
LED blinks once briefly within 2 seconds. | Synchronisation in progress (after Power up) | |
LED blinks once briefly within 2 seconds. | Test mode is active | |
LED blinks twice briefly within 2 seconds. | Overpressure detected by sensor | |
LED blinks once (long) within 2 seconds. | Setpoint value or required position (override) not yet reached | |
LED remains on. | Regulated. Signalled as long as the actuator does not rotate to readjust the setpoint value | |
LED blinks twice (long) within 2 seconds. | Required position (override) has been reached |
The flashing signal appears every 2 seconds. 1 = LED is illuminated, 0 = LED is not illuminated
Starting a test run for control components on VAV terminal units type TVE
Pressing the LED push button for > 2 s starts a test run.
Description of status LEDs and error messages regarding control components for terminal units LVC, TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ and TVA
LED | Operating status |
---|---|
OFF |
|
ON | Flow rate setpoint value has been reached |
Blinking slowly (0.5 Hz) |
or
|
Blinking rapidly (2.5 Hz) | Direction of rotation has been changed |
Easy controllers for VAV terminal units
VAV terminal units | Type | Part number |
---|---|---|
LVC | LMV-D3AL-F TR | M466EU1 |
TVE | TR0VE-024T-05l-DD15 | A00000069228 |
TVR | LMV-D3A-F TR | M466ES1 |
TVR | 227V-024T-05-002 | M466DC3 |
TZ-Silenzio, TA-Silenzio, TVZ, TVA | LMV-D3A TR | M466ES2 |
TZ-Silenzio, TA-Silenzio, TVZ, TVA | 227V-024T-05-002/RE20 | A00000089738 |
TVJ and TVT up to 1000 × 500 | 227V-024T-15-002 | A00000053055 |
TVT from 1000 × 600 | SMV-D3A TR | M466ES3 |
Easy controller LMV-D3AL-F TR for VAV terminal unit LVC
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 3.5 VA max. |
Power rating (DC) | 2 W max. |
Run time for 90° | 120 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU |
Easy controller TR0VE-024T-05I-DD15 for VAV terminal unit TVE
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | NW 100 - 200: 4 VA max. / NW 250 - 400: 7 VA max. |
Power rating (DC) | NW 100 - 200: 2.5 W max. / NW 250 - 400: 4 W max. |
Power consumption (when running/when idle) | 1 W |
Run time for 90° | 100 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 (with the terminal cover attached) |
EC conformity | EMC to 2014/30/EU |
Easy controller LMV-D3A TR for VAV terminal unit LVC
Easy controller LMV-D3A(-F) TR for VAV terminal units TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 5 VA max. |
Power rating (DC) | 2.5 W max. |
Run time for 90° | 110 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU |
Easy controller 227V-024T-05-002(/RE20) for VAV terminal units TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 5 VA max. |
Power rating (DC) | 3 W max. |
Run time for 90° | 100 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU |
Easy controller SMV-D3A TR for VAV terminal unit TVT from NW 1000 x 600
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3 W max. |
Run time for 90° | 110 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, max. 0.5 mA |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34
Contact
We are here for you
Please specify your message and type of request.
Tel.: +43 1 250 43-0 | Fax: +43 1 250 43 34
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +43 1 250 43-0| Fax: +43 1 250 43 34